Power strips & PDUs
for 19″ cabinets

From the Schuko strip with surge protection to the Smart PDU with metering per socket and remote switching — plus mounting brackets, holders and the PS-3U power distribution panel.

Request a quote Configure a cabinet with accessories

From the simple strip to the Smart PDU

Power distribution in the rack has a big say in how well a cabinet can be operated. For the network cabinet in the office, a basic power strip with a switch and surge protection is enough. In the data centre, by contrast, every kilowatt hour counts: Smart PDUs measure energy at the input or per socket, report limit values via SNMP and switch individual sockets remotely.

Basic PDU: 19″ power strips, 16 A

The strips for horizontal installation in 1 U: body of anodised aluminium, mains cable 3 m (1.5 mm²), removable metal holders for mounting at four levels. Three versions, each with Schuko or French UTE sockets:

  • LZ-30/9 — 9 sockets, without additional functions.
  • LZ-211 — 6 sockets with illuminated switch.
  • LZ-30F — 6 sockets with illuminated switch, surge protection and interference filter.
LZ-211 Schuko – 6 sockets, illuminated switch, 19″/1 U
LZ-211 Schuko6 sockets, illuminated switch, 19″/1 U
TypeSocketsIlluminated switchSurge protection + filterBody (L × W × H)Catalogue number
LZ-30/99 × UTE435.6 × 44 × 44.4 mmW-LZI30-09-00-000
LZ-30/9 Schuko9 × Schuko435.6 × 44 × 44.4 mmW-LZI30-09-SU-000
LZ-2116 × UTE✔435.6 × 44 × 56.9 mmW-LZ21-10-00-000
LZ-211 Schuko6 × Schuko✔435.6 × 44 × 56.9 mmW-LZ21-10-SU-000
LZ-30F6 × UTE✔✔435.6 × 44 × 56.9 mmW-LZ30-F0-00-000
LZ-30F Schuko6 × Schuko✔✔435.6 × 44 × 56.9 mmW-LZ30-F0-SU-000

230 V AC, max. 16 A / 3680 W, IP 20. Mains cable 3 m black, other lengths from 1 to 5 m as special order. Supplied with holders and fixings.

Request with the enclosure →or individually for retrofitting

Smart PDU: measure, monitor, switch

The intelligent power strips are configured to the application: housing of aluminium or stainless steel (standard black RAL 9004, any other RAL colour possible), sockets C13, C19, IEX, Schuko or UTE, single- or three-phase up to 32 A, mains cable 3 m with IEC 60309 plug. Protection is provided by hydraulic-magnetic circuit breakers.

The IEX socket deserves a sentence of its own: it accepts both C14 and C20 plugs without adapters — with locking, so that no power cable comes loose while you work in the cabinet. If you do not know today which devices will be in the rack in three years, you will not plan in the wrong socket.

IEX sockets – for C14 and C20 plugs, lockable
IEX socketsfor C14 and C20 plugs, lockable
Lite Controller – type PIML: 7-segment display, 1 × Ethernet
Lite Controllertype PIML: 7-segment display, 1 × Ethernet
Advanced Controller – OLED display, 2 × Gigabit, hot-swap
Advanced ControllerOLED display, 2 × Gigabit, hot-swap

Seven specification levels

FunctionWPMPIMLPIMPOMPOSPOMS
Housing, switch, sockets (C13, C19, IEX, UTE, Schuko)✔✔✔✔✔✔✔
Energy metering at the input (kWh, W, VA, VAR, A, V, PF, Hz), RCM optional✔✔✔✔✔✔
Remote access, alarm thresholds, environmental sensors (EMD)✔✔✔✔✔
Advanced Controller: hot-swap, 2 × Gigabit, cascade of up to 16 PDUs✔✔✔✔
Energy metering per socket✔✔
Remote switching of sockets, switch-on delay, LED per socket✔✔

B = Basic (no electronics) · PM = built-in energy meter with display · PIML = monitoring at the input, Lite · PIM = monitoring at the input · POM = input + per socket · POS = input + socket management · POMS = input + per socket + socket management.

  • Environmental monitoring: up to 8 EMD sensors (temperature/humidity) in cascade, two digital inputs per sensor for water leak, door, smoke, vibration or motion detectors.
  • Cascading: up to 16 PDUs on one IP address (Advanced Controller), saves network ports.
  • Measurement accuracy: kWh measurement ±1 % — for billing by consumer in colocation operation.
  • Protocols: SNMP v1/v2c/v3, Modbus, HTTPS, SSH v2, RADIUS, Syslog, SMTP, IPv4/IPv6 and others.

Example configurations

The catalogue number contains a free field _ for the type code (B, PM, PIML, PIM, POM, POS or POMS). We put together other configurations — socket mix, colour, cable length — on request.

SupplySwitchSocketsCatalogue number (insert type)
single-phase, 230 V, 16 A—18 × IEXW-LZ-_11618IEX
single-phase, 230 V, 16 A—20 × C13 + 4 × C19W-LZ-_11620C134C19
single-phase, 230 V, 32 A224 × IEXW-LZ-_13224IEX
380–415 V, 16 A—24 × IEXW-LZ-_31624IEX
three-phase, 380–415 V, 32 A636 × IEXW-LZ-_33236IEX
three-phase, 380–415 V, 32 A630 × C13 + 6 × C19W-LZ-_33230C136C19

Switch = hydraulic-magnetic circuit breakers. Conductor cross-section: 1-phase 16 A 1.5 mm², 3-phase 16 A 2.5 mm², 32 A 4.0 mm². Degree of protection IP 20.

Request with the enclosure →or individually for retrofitting

Holders and mounting brackets

Vertically mounted strips need a bracket in the side space. In SZB IT 800 mm wide, the mounting bracket LZ does this over the full cabinet height; on the open racks SRD and SRX the strips sit on the holders LZ — short for one, long for two power strips.

Power strips on the open rack – mounted vertically with holders LZ
Power strips on the open rackmounted vertically with holders LZ
ItemApplicationRAL 7035RAL 9005
Holder LZ, shortSRD/SRX, 1 power stripW-5367-53-01-011W-5367-53-01-161
Holder LZ, longSRD/SRX, 2 power stripsW-5367-53-02-011W-5367-53-02-161
Mounting bracket LZ, 42 USZB IT, 800 mm wideW-5367-52-03-011W-5367-52-03-161
Mounting bracket LZ, 45 USZB IT, 800 mm wideW-5367-52-02-011W-5367-52-02-161
Mounting bracket LZ, 47 USZB IT, 800 mm wideW-5367-52-01-011W-5367-52-01-161

Powder-coated sheet steel, supplied with fixings, packaging unit 1 pc.

Request with the enclosure →or individually for retrofitting

Power distribution panel PS-3U

If fuses, power supplies or relays have to go on a DIN rail in the rack: the PS-3U is a 19″ panel with 3 U (133 mm), 60 mm depth and a 35 mm DIN rail for up to 22 DIN-rail-mounted devices with a module width of 17.5 mm. The cover has an opening of 402.5 × 45.5 mm for the controls. It comes empty as standard — fitted to your documentation on request.

As a special version ZPAS also builds the PRS-3U for supplying safety-critical loads: two three-phase sections, infeed per phase via Powercon NAC3 (max. 20 A), up to 24 lockable C13 outputs and max. 15 miniature circuit breakers, up to 4500 VA per phase.

PS-3U fitted – example with 48 V miniature circuit breakers
PS-3U fittedexample with 48 V miniature circuit breakers
PRS-3U – Powercon infeed, lockable C13 outputs
PRS-3UPowercon infeed, lockable C13 outputs
VersionRAL 7035RAL 9005
PS-3U, empty (mounting plate, DIN rail, housing, fixings)W-PS3U-00-00-011W-PS3U-00-00-161

Fitted panels and other dimensions on request.

Request with the enclosure →or individually for retrofitting

Frequently asked questions

What is the difference between PIM, POM and POMS?

PIM measures the energy at the input of the strip. POM also measures every individual socket — important when power is billed per device or customer. POMS can additionally switch the sockets remotely, e.g. to restart a frozen device.

Which plugs fit the IEX socket?

Standard C14 and C20 plugs, without adapters. A removable insert locks C14 plugs; C20 plugs with P-Lock or V-Lock click in directly. Matching cables C14–C13, C20–C14, C20–C19 and C20–C15 are available in 0.5 to 4 m.

How are power strips fixed in a server rack?

Horizontally in the 19″ grid with the supplied holders (mounting at four levels possible) or vertically in the side space: in the 800 mm wide SZB IT on the mounting bracket LZ, on the open racks SRD/SRX with the holders LZ.

Can the PDUs be connected to a monitoring system?

Yes — all network-capable types support SNMP v1/v2c/v3 and Modbus.

All questions in the FAQ →

Planning the power distribution for your rack?

Tell us the protection, phases, number of sockets and the monitoring you want — we will put the PDU together. Quotation within 2 working days at most.