How the calculator works
The calculator balances the power loss Pv of the installed equipment against the heat that flows through the enclosure walls. The basis is the guide value according to IEC 60890 with simplified effective surface areas, dimensions in metres.
- Effective surface area A: free-standing or roof installation A = 1.8 · H · (W + D) + 1.4 · W · D; in a row A = 1.4 · W · H + 1.8 · H · D + 1.4 · W · D; wall-mounted A = 1.4 · W · (H + D) + 1.8 · H · D.
- Heat transfer coefficient k: sheet steel, painted 5.5 W/m²K, stainless steel 4.5, aluminium, single-walled 12, aluminium, double-walled (SZD outdoor) 3.5, plastic/GRP 3.5.
- Temperature difference: ΔT = maximum ambient temperature − maximum permissible internal temperature.
- Cooling capacity: if the surroundings are warmer than permissible inside (ΔT ≥ 0), Q = Pv + k · A · ΔT applies. If they are cooler, the enclosure dissipates heat: Q = Pv − k · A · |ΔT|, at least 0 W.
The solution follows from this: a filter fan only with cooler surroundings and IP 54, air flow V = 3.1 · Q / |ΔT| in m³/h, 900 m³/h at most. A heat exchanger likewise only with cooler surroundings, transfer Q / |ΔT| in W/K. With cooler surroundings, the calculator sizes the cooling unit for the full power loss, because the dissipation through the walls decreases as soon as it gets warmer outside. The display is rounded to 10 W; the intermediate values are under “Calculation”. Solar radiation is not included, see outdoor climate control.
Example: control cabinet on the factory floor
Inputs as in the quick start “Control cabinet, factory floor”: sheet-steel enclosure H 2.0 × W 0.8 × D 0.6 m, free-standing, indoors, IP 54, Pv = 800 W, ambient max. 35 °C, internal max. 45 °C.
- A = 1.8 · 2.0 · (0.8 + 0.6) + 1.4 · 0.8 · 0.6 = 5.04 + 0.67 = 5.71 m²
- ΔT = 35 − 45 = −10 K: the surroundings are cooler, the enclosure dissipates 5.5 · 5.71 · 10 = 314 W.
- Q = 800 − 314 = 486 W, displayed as 490 W.
- Filter fan: 3.1 · 486 / 10 = 151 m³/h; the recommendation is LV 300 (≈ 175 m³/h) with outlet filter GV.
At an ambient temperature of 50 °C the balance is reversed: ΔT = +5 K, heat ingress 5.5 · 5.71 · 5 = 157 W, Q = 957 W, displayed as 960 W. Fan and heat exchanger are ruled out; the recommendation is the cooling unit CVE11 (1,000 W).
Calculating the heating capacity for an electrical enclosure
In winter, the calculator compares the minimum ambient temperature with the internal temperature that should not be undershot, for example +5 °C as frost protection or +15 °C for electronics. The internal heat of the devices is deducted:
Heating capacity = k · A · (Tinside,min − Toutside,min) − Pv, at least 0 W.
If the system does not run continuously in winter, set Pv = 0, otherwise the heater will be undersized. The calculator rounds up to whole fan heaters of 400 W each with thermostat.
Example: outdoor cabinet in winter
Inputs as in the quick start “Outdoor enclosure”, but with Pv = 0 W: aluminium, double-walled (k 3.5), H 1.8 × W 1.2 × D 0.6 m, free-standing, outside min. −20 °C, inside min. +5 °C.
- A = 1.8 · 1.8 · (1.2 + 0.6) + 1.4 · 1.2 · 0.6 = 5.83 + 1.01 = 6.84 m²
- ΔT = 5 − (−20) = 25 K
- Heat loss = 3.5 · 6.84 · 25 = 599 W, heating capacity = 599 − 0 = 599 W, displayed as 600 W.
- Recommendation: 2 × enclosure fan heater 400 W with thermostat.
With the preset 1,200 W of power loss, the internal heat covers the loss completely and the calculator shows 0 W. Units and thermostats: enclosure heaters.