Outdoor enclosure cooling
from ventilation to heat pump
Four ways to get the heat out of an outdoor cabinet — and one that also heats: ventilation panel, dual air circulation, cross-flow heat exchanger, cooling unit and the reversible AHP heat pump. Sized to IEC 60890 plus solar load, mounted ex works.
Request a quote Configure an outdoor cabinetOutdoors, thermal management is a must, not an accessory
At ZPAS, outdoor climate control is the thermal management for outdoor cabinets (IP54/IP55) and comprises forced ventilation with a ventilation panel, dual air circulation, cross-flow heat exchangers, CVO cooling units (550–5,800 W) and the reversible AHP heat pump — sized to IEC 60890 plus solar load, mounted and wired ex works. An outdoor cabinet works between two extremes: in summer the sun heats the cabinet on top of the power loss of the equipment; in winter there is a risk of frost and condensation, against which a thermostat-controlled enclosure heater protects. The double-walled SZD design, with its ventilated double wall, takes care of the solar load — for everything else there are four graded ways of dissipating heat, from the ventilation panel to the heat pump. Which one fits depends on the heat load, the location and one question: may it be warmer inside than outside? All options are available for the IP54 standard cabinets as well as for the IP55 outdoor enclosure — with a heat exchanger or cooling unit, the degree of protection is fully maintained thanks to the closed circuit.
The four ways — and the heat pump
Way 1: forced ventilation with a ventilation panel
For moderate heat loads, ventilation panels accelerate air circulation in the cabinet and in the enclosure shell. For cold nights, an air heater (400 W) works with a thermostat — so the equipment stays within the permissible window even in winter. This is the most economical stage: no refrigeration technology, hardly any maintenance.
Way 2: dual air circulation in full sun
If the cabinet is exposed to the sun, an external air circuit flows between the double walls of the door and side panels and carries away the solar heat — assisted by roof fans. The internal circuit cools the devices but remains completely separate from the outside air: dust and moisture do not reach the electronics.
Way 3: cross-flow heat exchanger and direct ventilation
With a high heat load, the cross-flow heat exchanger takes over: warm internal air and cool outside air flow separately through a radiator — the heat changes sides, while the air flows do not mix by design. If even more heat has to be removed (typically with UPS installations), direct ventilation comes into play: two fans of 510 m³/h each draw outside air through the double wall and filters.
Way 4: cooling unit — when it has to be cooler inside
Only when the internal temperature has to be below the outside temperature is active cooling required: CVO series compressor cooling units (550–5,800 W). Mounting depends on space and maintenance concept: inside the cabinet, recessed in the door or on the outside of the enclosure — internally mounted units sit on the door or on hinged side covers so that maintenance remains easy.
The premier class: the reversible AHP air heat pump
The AHP_35_Ti cools and heats with one unit — controlled by temperature and humidity measurement in the cabinet: 10–40 °C and 32–72 % relative humidity kept constant all year round, maintenance-free and more economical than a cooling unit plus electric heater. For larger loads: AHP 7.0 (7 kW cooling / 9 kW heating, −15 to +50 °C, IP 55).
Which way for which case?
| Method | Principle | When it makes sense | Winter |
|---|---|---|---|
| Forced ventilation | Ventilation panel, recirculation | moderate heat load, inside > outside permissible | Air heater 400 W + thermostat |
| Dual circulation | internal + external circuit, roof fans | strong solar radiation | Heater + thermostat |
| Heat exchanger / direct ventilation | Cross-flow heat exchanger or 2× 510 m³/h | high heat load, UPS installations | Heater + thermostat |
| CVO cooling unit | Compressor, 550–5,800 W | inside must be cooler than outside | separate heater |
| AHP heat pump | Reversible operation cooling/heating | constant climate all year round, energy efficiency | integrated |
Sizing follows IEC 60890 plus solar load — fastest with the cooling & heating capacity calculator. Delivery is complete: unit sized, mounted and wired ex works, thermostat and heater included if the site requires them — both in detail on the outdoor cabinet accessories page.
Outdoor cabinet catalogue (PDF, 64 pages) — all dimensional drawings, versions and catalogue numbers for ventilation, climate control and heat pumps.
Open catalogue (PDF) → · all catalogues in the download centre
Frequently asked questions — outdoor climate control
Is ventilation enough — or do you need a cooling unit?
As long as the internal temperature may be above the outside temperature, ventilation is usually sufficient (passive or with a ventilation panel). A cooling unit becomes necessary when it has to be cooler inside the cabinet than outside — typically with a high heat load in a confined space or sensitive electronics. Sizing fans and heat exchangers: filter fans & heat exchangers; solar load outdoors: electrical enclosures in the sun.
What does the AHP heat pump offer compared with a cooling unit plus heater?
The reversible air heat pump cools and heats with one unit and keeps temperature and humidity constant all year round with lower energy consumption than the combination of a conventional cooling unit and an electric heater. The AHP_35_Ti keeps 10–40 °C and 32–72 % relative humidity constant.
How is climate control for outdoor use sized?
To IEC 60890 from the power loss, cabinet surface area and permissible temperature rise — outdoors, the solar load is added. The cooling capacity calculator works through both and suggests the right unit; mounting and wiring are done ex works.
View completed outdoor projects
Eighteen delivered orders in pictures, seven of them on site — from the Formula 1 circuit in Jeddah to an installation in Togo. Plus special colours, rows up to 4,700 mm, roof-mounted climate control, 19-inch and electrical interior fit-outs.