Filter fans & heat exchangers
for electrical enclosures

Updated:

When a filter fan is enough and when a heat exchanger is better — with an airflow table, sizing formula and thermostat tips.

In short: filter fans and air/air heat exchangers dissipate heat as long as it is cooler outside than inside the enclosure. The filter fan is the most economical solution; the heat exchanger keeps dust and moisture out. ZPAS fits both at the factory and sizes them according to your power loss.

Which cooling for which electrical enclosure?

SolutionPrincipleLimitTypical application
Passive coolingHeat dissipated via the enclosure wallslow power lossDistribution boards, terminal boxes
Filter fanFiltered outside air through the enclosurealways warmer inside than outside; dust, moistureFactory hall, clean environment
Air/air heat exchangertwo separate air circuitsoutput = W/K × ΔT; only with cooler surroundingsdusty or humid environment
Cooling unitRefrigeration circuit with compressorenergy consumption, maintenanceinside must be cooler than outside

The cooling capacity calculator works out in one minute which solution is sufficient for your heat load — including solar load for enclosures outdoors.

Filter fans for electrical enclosures

A filter fan draws in ambient air through a filter mat, and an outlet filter on the opposite side lets the warm air escape. Fan at the bottom, outlet at the top — this way the airflow supports natural convection. For ZPAS enclosures we use filter fans of the LV series (Rübsamen & Herr) or equivalent, in 230 V or 115 V AC and 24 V DC.

TypeAirflow with outlet filterExternal dimensions
LV 25042 m³/h148 × 148 mm
LV 30090 m³/h204 × 204 mm
LV 400205 m³/h250 × 250 mm
LV 500235 m³/h250 × 250 mm
LV 550260 m³/h250 × 250 mm
LV 600385 m³/h323 × 323 mm
LV 700530 m³/h323 × 323 mm
LV 800610 m³/h323 × 323 mm

Values at 50 Hz with outlet filter according to the manufacturer’s catalogue. Free-blowing, the airflow is higher (LV 800: 930 m³/h) — for sizing, the value with filter is what counts.

How many fans does the enclosure need?

The required airflow is given by V = P ÷ (0.34 × ΔT) in m³/h. With 1,500 W power loss and a permissible temperature difference of 10 K, that is around 440 m³/h — i.e. one LV 700 or two smaller fans. If one fan is not enough, the outdoor configurator automatically distributes the output across several units.

Fans with thermostat

A thermostat with a normally open contact switches the fan on when the set temperature is exceeded; a normally closed contact, by contrast, switches a heater off. The thermostats from the ZPAS accessory range work with a bimetal element, setting range 0–60 °C, switching differential around 7 K, switching capacity 6 A at 250 V AC.

Air/air heat exchanger

The heat exchanger separates internal and outside air: two fans drive the air through separate channels of a heat exchanger block, and the heat passes through the wall to the outside. This keeps dust, oil and moisture out. Its output is stated in W/K and applies per kelvin of temperature difference:

Cooling capacity (W) = specific output (W/K) × (internal temperature − outside temperature)

A unit with 35 W/K therefore manages around 525 W at a difference of 15 K. We use heat exchangers of the Aertherm XVA series (Cosmotec) with 16, 35 or 50 W/K, or equivalent. With high loads or a small temperature difference, the heat exchanger reaches its limit — then a cooling unit or, outdoors, the outdoor air conditioner is the right choice.

Fitted at the factory

ZPAS supplies electrical enclosures and outdoor enclosures with ready-installed fans, heat exchangers, cooling units and heaters — cut-outs, assembly and wiring come from the factory. The right heater also helps against condensation: more on this in the guide condensation in electrical enclosures.

Frequently asked questions about fans and heat exchangers

Filter fan or heat exchanger — which is right?

A filter fan replaces the enclosure air with filtered ambient air — inexpensive and effective as long as the surroundings are cool and clean enough. An air/air heat exchanger works with separate circuits: no outside air enters the enclosure. Both only cool to just above the ambient temperature; if it has to be cooler inside than outside, you need a cooling unit.

How much airflow does an electrical enclosure need?

Rule of thumb: airflow (m³/h) = power loss (W) ÷ (0.34 × ΔT), where ΔT is the permissible difference between internal and outside temperature. Example: 500 W at ΔT = 10 K gives around 150 m³/h. Calculate with the airflow with outlet filter, not with the free-blowing value.

Is a fan with thermostat worthwhile?

Yes. A thermostat with a normally open contact only switches the fan on when the set temperature is exceeded — this saves energy, filter changes and noise. The thermostats from the ZPAS accessory range cover 0–60 °C, with a switching differential of around 7 K and 6 A at 250 V AC.

Is the degree of protection maintained with a filter fan?

With a filter mat, the LV series filter fans achieve IP 54. For outdoor use there is an IP 55 solution (LV/GV 250–800) with a finer filter, a UV-resistant outer grille and an optional stainless steel water-jet hood.

Fan, heat exchanger or cooling unit?

Tell us the power loss, ambient temperature and installation site — we will size the cooling and fit it at the factory.

Request a quote    Calculate cooling capacity