Electrical enclosure overheating?
Causes & solutions

Updated:

Calculate the cooling capacity you need — and find the right solution: filter fan, heat exchanger or cooling unit.

🌡️ Go straight to the cooling calculation →

Overheating is the most common cause of unplanned failures in electrical enclosures. Controllers crash, frequency inverters switch to protective mode and the service life of electronics drops sharply — a rule of thumb says: every sustained temperature rise of 10 °C halves the service life of electronic components. The good news: with the right climate control, the problem can be solved reliably and cost-effectively.

Short answer: An electrical enclosure overheats when the power loss (heat) generated inside is not dissipated sufficiently. Whether a filter fan is enough or a cooling unit is needed depends on the power loss and the ambient temperature: if the surroundings are cooler than the desired internal temperature, a filter fan is often sufficient. If the surroundings are just as warm or warmer, an active cooling unit is required.

Calculate the cooling capacity — the free online calculator

Enter the enclosure dimensions, power loss and temperatures — the calculator estimates the required cooling or heating capacity in real time (guide value based on IEC 60890) and directly recommends the right type of solution: filter fan, heat exchanger or cooling unit.

The interactive calculator has its own page — clearly laid out at full width:

🌡️ To the cooling & heating capacity calculator →

The most common causes of overheating

What overheating actually causes

How the calculator works — the rule of thumb in detail

Before choosing a cooling solution, you need to know how much heat actually has to be dissipated. This takes three steps:

  1. Add up the power loss: add up the power loss of all installed components (figures from the data sheets, in watts). Typical guide values: frequency inverter approx. 3–5 % of the drive power (7.5 kW inverter → ~300 W), power supplies 5–10 % of the output power, contactors/relays 2–10 W, PLC 10–50 W, transformers/chokes as per data sheet.
  2. Subtract the enclosure's own heat dissipation: the enclosure releases heat through its surface: Q [W] = k × A × ΔT with ΔT = internal minus ambient temperature. The heat transfer coefficient k depends on the material: painted sheet steel ≈ 5.5, stainless steel ≈ 3.7, single-walled aluminium ≈ 12, plastic ≈ 3.5 W/m²K. The effective surface area A (simplified according to IEC 60890, dimensions in metres) depends on the installation — e.g. free-standing A = 1.8·H·(W+D) + 1.4·W·D, wall-mounted A = 1.4·W·(H+D) + 1.8·D·H (W = width, D = depth); reduced areas apply to baying enclosures.
  3. Difference = required active cooling capacity: the heat generated by the components, minus the passive dissipation, has to be removed actively.

Example: enclosure 2.0 × 0.8 × 0.6 m, free-standing → A ≈ 5.7 m². With a hall at max. 35 °C and 45 °C permitted inside (ΔT = 10 K): Q ≈ 5.5 × 5.7 × 10 ≈ 315 W self-dissipation. If the enclosure contains 800 W of power loss, ~485 W must be removed actively — exactly what the online calculator works out for you.

Important — cooler than the surroundings is only possible with a cooling unit: a filter fan can never make the enclosure interior colder than the ambient air. If, for example, you want to keep a constant 35 °C in the enclosure but the hall is at 40 °C, no fan will help — a cooling unit (compressor) is then essential. For a precise design, we will be happy to do the calculation for you.

The solutions at a glance — which cooling, when?

Solution When suitable ZPAS component
Filter fan Surroundings cooler than the desired internal temperature, low to medium power loss. Inexpensive and low-maintenance. LV series: 15–930 m³/h, IP 54
Air/air heat exchanger Dusty or humid surroundings where no outside air may enter. Separates the internal and external air circuits. Wall-mounted or roof-mounted unit, IP 54
Cooling unit (compressor) Surroundings as warm as or warmer than the target internal temperature, high power loss. Maintains a defined internal temperature. Side-mounted unit CVE (310–5,800 W), roof-mounted unit ETE (330–2,700 W)
Air/water heat exchanger Very high heat loads and an existing cooling water circuit (e.g. in data centre or machine cooling). On request / custom build
Outdoor air conditioner / heat pump Outdoor cabinets exposed to sunlight — cool in summer, heat in winter. CVO (550–5,800 W), AHP 7.0 (−15 to +50 °C)

More on the relationship between degree of protection and installation site: → IP ratings explained. For high-load environments with several racks: → data centre and server room cooling. Detailed selection guide: → choosing a cooling unit for electrical enclosures & server racks.

Outdoors: sun and frost

Outdoor cabinets face two opposite problems: overheating from solar radiation in summer, condensation and frost in winter. Proven measures:

Details on weatherproof enclosures: → ZPAS outdoor enclosures & outdoor cabinets.

Common design mistakes

How ZPAS finds the right cooling for you

You do not have to do the design yourself. In the electrical enclosure configurator you select climate control components directly — filter fan, side-mounted cooling unit (CVE) and roof-mounted cooling unit (ETE) are available as options. For outdoor use, the outdoor enclosure configurator offers CVO air conditioners and a heat pump. Tell us your power loss and ambient conditions — we calculate the right cooling capacity and deliver the enclosure ready for operation from the factory.

About the author

Joachim Hennig · Head of Sales, ZPAS GROUP GmbH

Joachim Hennig is Head of Sales at ZPAS GROUP GmbH in Leipzig. He advises customers from industry, IT and telecommunications on the selection of electrical enclosures, server racks and outdoor enclosures — from standard enclosures to custom builds.

LinkedIn profile →  ·  info@zpasgroup.de

Electrical enclosure too hot? We will solve it.

Tell us the power loss, ambient temperature and installation site — you will receive a concrete cooling recommendation and a quotation within 2 working days at most. No obligation.

Request a quote    Configure electrical enclosure