IP65 or
IP66?

Updated:

Both degrees of protection are dust-tight. The difference lies solely in the water protection – and that decides whether IP65 is enough or IP66 is needed. Explained briefly according to EN 60529.

IP65 and IP66 in 30 seconds

The IP rating (International Protection) according to EN 60529 consists of two digits. The first stands for protection against foreign bodies and dust, the second for protection against water.

IP 6 _
1st digit = 6: dust-tight (no dust ingress)
IP _ 5
2nd digit = 5: protection against water jets from all directions
IP _ 6
2nd digit = 6: protection against powerful water jets from all directions

With IP65 and IP66 the first digit is the same: both enclosures are dust-tight. The only difference is the second digit – the strength of the water jet that the enclosure withstands in the test.

IP65 vs. IP66 compared directly

PropertyIP65IP66
Dust protection (1st digit)6 – dust-tight6 – dust-tight
Water protection (2nd digit)5 – water jets6 – powerful water jets
Test to EN 60529: nozzle⌀ 6.3 mm⌀ 12.5 mm
Flow rate12.5 l/min100 l/min
Nozzle distance3 m3 m
Typical applicationDamp and wash-down areas, cleanrooms, food industryDirect powerful water jets: washing installations, ports, offshore installations
ZPAS seriesSWN and SWN Inox (wall-mounted enclosures)no catalogue series

Test values from the table for the second digit in the guide to IP ratings. Neither IP65 nor IP66 protects against immersion; that is what digits 7 and 8 stand for.

What the difference means in practice

At 100 l/min, the test jet for IP66 delivers eight times the volume of water of the IP65 jet (12.5 l/min), from a nozzle roughly twice the size. For seals, door locks and cable entries, that is a considerably higher load. IP66 is therefore not a “better IP65” for every case, but the answer to a specific environment: water that hits the enclosure with force and in large quantities.

When it comes to dust, there is no difference. If you specify IP66 only because of a dusty environment, IP65 gives you the same protection. More on dust in the enclosure: Protecting electrical enclosures from dust.

Which degree of protection do you need?

At ZPAS: The SWN and SWN Inox wall-mounted enclosures have IP65. SZE3 is IP55 as standard, SZE2 is IP54 (IP55 with floor seal). The SZD outdoor series is IP54, IP55 on request. ZPAS does not list a series with IP66 in its catalogue.

IP65 at ZPAS: the SWN wall-mounted enclosure

The SWN wall-mounted enclosure is the ZPAS series with IP65 to EN 60529: a welded sheet-steel body in 20 standard sizes from 300 × 200 to 1000 × 800 mm, with a galvanised mounting plate. The multi-folded channel on the body holds back water and dust even when the door is open. The standard version in RAL 7035 is intended for indoor use.

For corrosive atmospheres and hygiene areas there is the SWN Inox in stainless steel 1.4301 (AISI 304), likewise with IP65. Design and sizes correspond to the standard SWN. More on the stainless steel enclosures page.

For permanent installation in the open air, the double-walled SZD outdoor cabinets are designed for IP54, IP55 on request. Why the design counts for more there than a high IP digit is explained in the guide IP54 or IP55?

More on this topic: All IP ratings (IP00–IP68) · Aluminium, steel or stainless steel? · Corrosion protection for electrical enclosures

About the author

Joachim Hennig · Sales Director, ZPAS GROUP GmbH

Joachim Hennig is Sales Director at ZPAS GROUP GmbH in Leipzig. He advises customers from industry, IT and telecommunications on the selection of electrical enclosures, server racks and outdoor enclosures – from standard enclosures to custom designs.

LinkedIn profile →  ·  info@zpasgroup.de

Not sure which degree of protection your project needs?

Tell us the installation site and ambient conditions – we will recommend the right degree of protection and series. Direct from the manufacturer.

Request a quote    Configure a cabinet