SZE2 baying enclosure
welded · IP 54/55
The welded baying enclosure for indoor and outdoor installations: 26 standard sizes from 600 to 1200 mm wide, mounting plate up to 1,000 kg, rail frame up to 1,600 kg, EMC special version — configurable and fitted out at the factory.
Request a quote Configure an enclosureThe welded baying enclosure for indoor and outdoor use
The SZE2 is the workhorse of the electrical enclosure range: a welded sheet-steel baying enclosure in 26 standard sizes (600–1200 mm wide, 2000/2200 mm high) — plus special sizes such as 1800 mm height and stainless steel on request. The design is built for easy baying; it can be supplied fitted out, wired and with a UL certificate of conformity, direct from the factory. The bolted alternative with IP 55 as standard is the SZE3. The direct comparison: baying enclosure: SZE2 or SZE3?
Design, degree of protection & equipment
A welded frame built as a system
The side frames carry cut-outs for mounting rails or the mounting plate. Roof openings for cables and fan systems are closed with blanking covers, the floor openings with sliding plates — cable entry without any sheet-metal work.
Up to 1,600 kg load capacity
1,000 kg on the mounting plate, 1,600 kg on the mounting rail frame, 150 kg on the swing frame, 20 kg on the door — ample reserve for heavy incoming supplies and transformers.
IP 54 — IP 55 with floor seal
Standard version with side panels: IP 54 to EN 60529. With an additional floor plate seal the protection rises to IP 55 — the economical answer to dusty and damp environments.
Door variants & locks
Front door with double-bit lock as standard, optionally a swing handle with profile half-cylinder; single or double door depending on the width, plus glass and solid sheet-steel doors from the door range.
EMC-tested version
For interference-sensitive applications the SZE2 is available as an EMC special version — its electromagnetic compatibility was tested at the Wrocław University of Science and Technology. The basics are covered in the EMC guide.
Modular system & baying
The modular system adds standardised interior modules to the baying suite; floor plate and roof plate variants cover project-specific cable routes. The enclosure suite grows with the installation.
Standard sizes table: the 26 standard sizes
Catalogue numbers of the standard version — enclosures 600 and 800 mm wide have a single door, those 1000 and 1200 mm wide a double door. Width with flush or protruding side panels, heights 2000 and 2200 mm (without plinth). · SZE2 datasheet (PDF, 1 page)
| Width, flush [mm] | Width, protruding [mm] | Depth [mm] | Height 2000 | Height 2200 |
|---|---|---|---|---|
| 600 | 650 | 400 | WZ-SZE2-2050-S10A-00-111-00-0-011 | — |
| 600 | 650 | 500 | WZ-SZE2-2012-S10A-00-111-00-0-011 | WZ-SZE2-2212-S10A-00-111-00-0-011 |
| 600 | 650 | 600 | WZ-SZE2-2011-S10A-00-111-00-0-011 | WZ-SZE2-2211-S10A-00-111-00-0-011 |
| 600 | 650 | 800 | WZ-SZE2-2010-S10A-00-111-00-0-011 | WZ-SZE2-2210-S10A-00-111-00-0-011 |
| 800 | 850 | 400 | WZ-SZE2-2049-S10A-00-111-00-0-011 | — |
| 800 | 850 | 500 | WZ-SZE2-2009-S10A-00-111-00-0-011 | WZ-SZE2-2209-S10A-00-111-00-0-011 |
| 800 | 850 | 600 | WZ-SZE2-2008-S10A-00-111-00-0-011 | WZ-SZE2-2208-S10A-00-111-00-0-011 |
| 800 | 850 | 800 | WZ-SZE2-2007-S10A-00-111-00-0-011 | WZ-SZE2-2207-S10A-00-111-00-0-011 |
| 1000 | 1050 | 500 | WZ-SZE2-2006-S10A-00-111-00-0-011 | WZ-SZE2-2206-S10A-00-111-00-0-011 |
| 1000 | 1050 | 600 | WZ-SZE2-2005-S10A-00-111-00-0-011 | WZ-SZE2-2205-S10A-00-111-00-0-011 |
| 1000 | 1050 | 800 | WZ-SZE2-2004-S10A-00-111-00-0-011 | WZ-SZE2-2204-S10A-00-111-00-0-011 |
| 1200 | 1250 | 500 | WZ-SZE2-2003-S10A-00-111-00-0-011 | WZ-SZE2-2203-S10A-00-111-00-0-011 |
| 1200 | 1250 | 600 | WZ-SZE2-2002-S10A-00-111-00-0-011 | WZ-SZE2-2202-S10A-00-111-00-0-011 |
| 1200 | 1250 | 800 | WZ-SZE2-2001-S10A-00-111-00-0-011 | WZ-SZE2-2201-S10A-00-111-00-0-011 |
Enclosure systems catalogue (PDF, 124 pages) — all dimensional drawings, door, floor and roof variants and the complete SZE2 accessory range (p. 8–59).
Open catalogue (PDF) → · all catalogues in the download centre
Frequently asked questions — SZE2
Is the SZE2 rated IP 54 or IP 55?
IP 54 in the standard version with side panels. With an additional floor plate seal the SZE2 achieves IP 55 — both to EN 60529. What the difference means in practice is explained in the IP54/IP55 guide.
What is included in the scope of delivery — and what is not?
Standard version: frame, front door with double-bit lock, rear panel, mounting plate over the full enclosure height, sliding floor plates and blanking plates for the roof. Side panels, plinth, roof and lifting eyes are ordered separately — most easily in the configurator.
How much load does the SZE2 carry?
1,000 kg on the mounting plate, 1,600 kg on the mounting rail frame, 150 kg on the swing frame and 20 kg on the door.
Configure the SZE2 or send an enquiry?
Choose series, dimensions, door and accessories online — or simply send an informal enquiry: quotation within 2 working days at most.