Mounting system for electrical enclosures
Plate, rails, module system
Mounting plate with guides and supports, CLASSIC and UNI rail systems for the SZE2, mounting rails A, B and C for the SZE3, profile rails II with TS 35 DIN rail and the ZPAS module system – with lengths, key data and catalogue numbers.
Request a quote Configure electrical enclosure



Mounting plate, rail frame or module system?
The mounting plate is the simplest mounting level: a continuous galvanised surface, 3 mm thick, on which devices, cable ducts and DIN rails are screwed directly. Rail systems, by contrast, build a frame inside the enclosure – with levels at any depth and for higher loads. The module system is the special form for distribution boards: modular devices on DIN rails behind module panels that protect against contact.
Mounting plate, guides and supports
On both series the mounting plate is made of 3 mm galvanised sheet steel (normal sheet tolerances to EN 10143) and is supplied with the fixing elements for installation. On request ZPAS makes it powder-coated – in RAL 7035 or another colour –, as a swing-out version with hinges or from Textolite. The exact plate dimensions are shown in the dimensional drawings of the enclosures (SZE2: catalogue p. 17, SZE3: p. 69).
Guides (set of 2, fixed to the floor plate) make it easier to insert and align the plate. On the SZE3 the plate is positioned steplessly in the enclosure depth by means of guides and supports; if it is to sit at the rear between the vertical frame profiles, two additional supports are required.




Mounting plate
| Cabinet width | SZE2 | SZE3 |
|---|---|---|
| Enclosure height 2000 mm | ||
| 600 mm | W-1951-67-10-000-BP | W-6282-33-08-000 |
| 800 mm | W-1951-67-07-000-BP | W-6282-33-07-000 |
| 1000 mm | W-1951-67-04-000-BP | W-6282-33-06-000 |
| 1200 mm | W-1951-67-01-000-BP | W-6282-33-05-000 |
| Enclosure height 2200 mm | ||
| 600 mm | W-4950-28-10-000-BP | W-6282-33-04-000 |
| 800 mm | W-4950-28-07-000-BP | W-6282-33-03-000 |
| 1000 mm | W-4950-28-04-000-BP | W-6282-33-02-000 |
| 1200 mm | W-4950-28-01-000-BP | W-6282-33-01-000 |
Mounting plate guides (set of 2)
| Rack depth | SZE2 | SZE3 |
|---|---|---|
| 400 mm | W-1951-64-04-000 | W-6282-35-04-000 |
| 500 mm | W-1951-64-03-000 | W-6282-35-03-000 |
| 600 mm | W-1951-64-02-000 | W-6282-35-02-000 |
| 800 mm | W-1951-64-01-000 | W-6282-35-01-000 |
Mounting plate supports – SZE3 only


| Version | Packing unit | Catalogue number |
|---|---|---|
| Two supports (right and left) with fixing elements, for the plate at the rear between the vertical frame profiles | 1 set | W-6282-36-00-000 |
Mounting plate: packing unit 1 pc., guides: 1 set. Guides and supports made of galvanised sheet steel, with fixing elements.
Mounting plate connector for the enclosure row
In bayed enclosures it joins the mounting plates into a continuous mounting level across the enclosure boundary – galvanised sheet steel, with fixing accessories.


| Rack height | SZE2: dimensions H × W × D | SZE2 | SZE3 |
|---|---|---|---|
| 2000 mm | 1867 × 86 × 30 mm | W-1951-47-01-000 | W-6282-24-02-000 |
| 2200 mm | 2067 × 86 × 30 mm | W-4950-30-00-000 | W-6282-24-01-000 |
Packing unit 1 pc. Partition walls and baying accessories for the enclosure row can be found under Doors, panels, roof & plinths.
CLASSIC and UNI rail systems for the SZE2
There are two rail systems for the SZE2, which use the same fixing sets and can be combined. CLASSIC works with supports: cross members are inserted into the horizontal or vertical perforations of the enclosure frame, vertical supports are fixed to the floor and roof plates; the CLASSIC mounting rails, available in 25 lengths from 200 to 1200 mm, sit on these supports. This allows mounting levels to be built at any position in the enclosure.
UNI is the universal profile: its perforation matches both the horizontal and the vertical perforations in the enclosure frame, and the standard lengths are matched to the height, width and depth of the enclosures – other lengths are cut to size on request. With the angle connector they form any kind of frame; UNI also carries the 19″ frame and the profile rails II of the module system. For the mounting rail frame of the SZE2 the catalogue states a load capacity of 1,600 kg (mounting plate: 1,000 kg).





CLASSIC mounting rail
For fixing to cross members and vertical supports. Matched to the enclosure width: 550 mm (enclosure 600 mm), 750 mm (800), 950 mm (1000) and 1150 mm (1200).
| Length | Catalogue number | Length | Catalogue number |
|---|---|---|---|
| 200 mm | W-0573-12-25-000 | 650 mm | W-0573-12-13-000 |
| 225 mm | W-0573-12-24-000 | 700 mm | W-0573-12-12-000 |
| 250 mm | W-0573-12-23-000 | 750 mm | W-0573-12-11-000 |
| 275 mm | W-0573-12-22-000 | 775 mm | W-0573-12-10-000 |
| 300 mm | W-0573-12-21-000 | 800 mm | W-0573-12-09-000 |
| 350 mm | W-0573-12-20-000 | 850 mm | W-0573-12-08-000 |
| 400 mm | W-0573-12-19-000 | 900 mm | W-0573-12-07-000 |
| 450 mm | W-0573-12-18-000 | 950 mm | W-0573-12-06-000 |
| 500 mm | W-0573-12-17-000 | 1000 mm | W-0573-12-05-000 |
| 525 mm | W-0573-12-16-000 | 1050 mm | W-0573-12-04-000 |
| 550 mm | W-0573-12-15-000 | 1100 mm | W-0573-12-03-000 |
| 600 mm | W-0573-12-14-000 | 1150 mm | W-0573-12-02-000 |
| – | – | 1200 mm | W-0573-12-01-000 |
CLASSIC cross member
Fixed to the vertical or horizontal perforations in the enclosure frame.
| Enclosure size | Support length | Catalogue number |
|---|---|---|
| Installation across the width | ||
| 600 mm | 552.5 mm | W-1951-46-08-000 |
| 800 mm | 752.5 mm | W-1951-46-07-000 |
| 1000 mm | 952.5 mm | W-1951-46-06-000 |
| 1200 mm | 1152.5 mm | W-1951-46-05-000 |
| Installation across the depth | ||
| 400 mm | 240 mm | W-1951-46-04-000 |
| 500 mm | 340 mm | W-1951-46-03-000 |
| 600 mm | 440 mm | W-1951-46-02-000 |
| 800 mm | 640 mm | W-1951-46-01-000 |
CLASSIC vertical support
For fixing to the floor and roof plates of the enclosure frame – according to the catalogue either indirectly via UNI mounting rails (W-1951-19-05-000 to W-1951-19-08-000), directly on the roof or floor plate, or directly on the vertical profiles of the enclosure frame.
| Rack height | Support length | Catalogue number |
|---|---|---|
| 2000 mm | 1875 mm | W-1951-48-01-000 |
| 2200 mm | 2075 mm | W-1951-48-05-000 |
mounting rail UNI
Standard lengths according to enclosure size; other lengths on customer request, also cut to size individually.
| Enclosure size | Rail length | Catalogue number |
|---|---|---|
| Vertical – for enclosure height | ||
| 1200 mm | 1075 mm | W-1951-19-04-000 |
| 1600 mm | 1475 mm | W-1951-19-03-000 |
| 1800 mm | 1675 mm | W-1951-19-02-000 |
| 2000 mm | 1875 mm | W-1951-19-01-000 |
| 2200 mm | 2075 mm | W-4950-31-00-000 |
| Horizontal across the width – for enclosure width | ||
| 600 mm | 562.5 mm | W-1951-19-08-000 |
| 800 mm | 762.5 mm | W-1951-19-07-000 |
| 1000 mm | 962.5 mm | W-1951-19-06-000 |
| 1200 mm | 1162.5 mm | W-1951-19-05-000 |
| Horizontal across the depth – for enclosure depth | ||
| 400 mm | 300 mm | W-1951-19-12-000 |
| 500 mm | 400 mm | W-1951-19-11-000 |
| 600 mm | 500 mm | W-1951-19-10-000 |
| 800 mm | 700 mm | W-1951-19-09-000 |
Angle connectors for UNI mounting rails

| Version | Packing unit | Catalogue number |
|---|---|---|
| Connector for UNI mounting rails, galvanised, without fixing accessories | 1 pc. | W-1951-21-00-000 |
All rails and supports made of galvanised sheet steel, supplied without fixing accessories (see fixing accessories), packing unit 1 pc.
Fixing accessories: thread-forming screws and cage nuts
CLASSIC, UNI and the SZE3 mounting rails are screwed together with the same sets of 20 pieces. The thread-forming screw M6 × 16 (W-1951-44-01-000) connects the mounting rails to the enclosure frame and to each other. Depending on the connection point, the catalogue alternatively provides for a screw M6 × 16 with cage nut M6 or with nut M6 and washers – the overview on catalogue page 40 shows which point is screwed in which way. For the SZE3 there are also cage nuts M8 with wing tabs, with which devices are fixed directly to the enclosure frame.




| set | Contents | Packing unit | Catalogue number |
|---|---|---|---|
| Thread-forming screw | Screw M6 × 16 – 20 pcs | 1 set | W-1951-44-01-000 |
| Screw with cage nut | Screw M6 × 16, cage nut M6, washer 6.4 – 20 pcs each | 1 set | W-1951-44-02-000 |
| Screw with nut | Screw M6 × 16 – 20 pcs, nut M6 – 20 pcs, washer 6.4 – 40 pcs | 1 set | W-1951-44-03-000 |
| Cage nut M8 (SZE3) | Cage nut M8 with wing tabs – 10 pcs | 1 set | W-M1F-03-0165-000 |
Sets W-1951-44-01-000 and W-1951-44-02-000 apply to the SZE2 and SZE3. The mounting set for profile rails II and 19″ profile rails is listed under profile rails II.
Mounting rails A, B and C for the SZE3
The SZE3 frame is perforated on two levels in a 25 mm grid – with Ø 5.4 mm openings for thread-forming screws M6 and 10.5 × 16.5 mm openings for cage nuts M8 with wing tabs. The mounting rails are matched to this: type A and type B build frames inside the enclosure and differ in the way they are fixed; with thread-forming screws M6 they can also be connected to each other. Mounting rail C fixes the 19″ profile rails to the enclosure frame.




Mounting rails type A and type B
| Enclosure width or depth* | Type A: length | Type A | Type B: length | Type B |
|---|---|---|---|---|
| – | 262 mm | W-6282-40-10-000 | 206 mm | W-6282-42-10-000 |
| 400 mm | 362 mm | W-6282-40-09-000 | 306 mm | W-6282-42-09-000 |
| 500 mm | 462 mm | W-6282-40-08-000 | 406 mm | W-6282-42-08-000 |
| 600 mm | 562 mm | W-6282-40-07-000 | 506 mm | W-6282-42-07-000 |
| – | 662 mm | W-6282-40-06-000 | 606 mm | W-6282-42-06-000 |
| 800 mm | 762 mm | W-6282-40-05-000 | 706 mm | W-6282-42-05-000 |
| – | 862 mm | W-6282-40-04-000 | 806 mm | W-6282-42-04-000 |
| 1000 mm | 962 mm | W-6282-40-03-000 | 906 mm | W-6282-42-03-000 |
| – | 1062 mm | W-6282-40-02-000 | 1006 mm | W-6282-42-02-000 |
| 1200 mm | 1162 mm | W-6282-40-01-000 | 1106 mm | W-6282-42-01-000 |
* for horizontal fixing between the posts of the enclosure frame; “–” = length without an assigned enclosure size. Galvanised sheet steel, without fixing accessories, packing unit 1 pc.
Mounting rail C – for the 19″ frame
Carries the 19″ profile rails in the SZE3; in 800 mm wide enclosures, additional brackets (W-5205-90-00-C12) establish the 19″ dimension. Profile rails and cross members are listed under 19″ accessories.
| Enclosure width or depth | Length | Catalogue number |
|---|---|---|
| 400 mm | 306 mm | W-6282-43-06-000 |
| 500 mm | 406 mm | W-6282-43-05-000 |
| 600 mm | 506 mm | W-6282-43-04-000 |
| 800 mm | 706 mm | W-6282-43-03-000 |
| 1000 mm | 906 mm | W-6282-43-02-000 |
| 1200 mm | 1106 mm | W-6282-43-01-000 |
Galvanised sheet steel, without fixing accessories, packing unit 1 pc.
Profile rails II and TS 35 DIN rail
Profile rails II form the frame for modular devices in the SZE2: mounting brackets, 35 mm DIN rails and module panels are fitted to them. They sit on four UNI mounting rails whose length matches the enclosure depth – so the depth of the level can be adjusted steplessly. A mounting set fixes one pair of profile rails II (or 19″ profile rails) to the UNI rails.
The TS 35 DIN rail (15 mm deep, galvanised) is fitted to the profile rails II with two mounting brackets. For equipment that places heavy loads on the rails, the catalogue provides other constructions in 1000 and 1200 mm wide enclosures – we will advise you on this in your project.




Profile rails II
| Rack height | Capacity* | Packing unit | Catalogue number |
|---|---|---|---|
| 2000 mm | 12 DIN rails | 2 pcs | W-4881-67-02-000 |
| 2200 mm | 14 DIN rails | 2 pcs | W-4881-67-04-000 |
* maximum number of installed 35 mm DIN rails. Galvanised sheet steel, without mounting elements.
Mounting set for profile rails II and 19″ profile rails
| Contents | Packing unit | Catalogue number |
|---|---|---|
| Screw M6 × 16 – 4 pcs, nut M6 – 4 pcs, washer – 8 pcs, toothed lock washer – 4 pcs (for one pair of rails on UNI mounting rails) | 1 set | W-SB00-37-04-000 |
TS 35 DIN rail and mounting brackets
| Version | For enclosure width | Catalogue number |
|---|---|---|
| TS 35 DIN rail | 600 mm | W-0573-52-24-000 |
| TS 35 DIN rail | 800 mm | W-0573-52-23-000 |
| TS 35 DIN rail | 1000 mm | W-0573-52-22-000 |
| TS 35 DIN rail | 1200 mm | W-0573-52-21-000 |
| Mounting bracket (1 pc.) | all | W-0573-52-30-000 |
DIN rail without mounting elements, packing unit 1 pc. Mounting brackets galvanised, with elements for fitting to profile rail II and DIN rail; 2 brackets are required per rail.
ZPAS module system for distribution boards in the SZE2
The module system turns the SZE2 into a distribution board: the modular devices sit on DIN rails, with module panels 150 mm high in front of them, fixed directly to the profile rails II. Installations in this version have the degree of protection IP 30 against contact with live parts, the closed SZE2 IP 54.
Planning is done in field-height modules (MFH), 1 MFH = 150 mm. An installation with a busbar system generally has three zones: busbars (3 MFH), device mounting (8 MFH in the 2000 mm high enclosure) and cable entry (1 MFH + 100 mm). A 2000 mm high enclosure therefore takes 288 modules of 18 mm at 600 mm width, 432 at 800 mm and 576 at 1000 and 1200 mm.
Remaining areas are closed by blank module plates 150, 100 and 50 mm; depending on the enclosure height, a plate of a different height is required – 50 mm in the 1800 mm high enclosure, 100 mm in the 2000 mm high enclosure. Cover strips conceal the vertical and horizontal gaps between profile rails II and the enclosure frame. Panels, blank plates and cover strips are powder-coated in RAL 7035. For electricity meters there is a meter tray for mounting on profile rails II.





Module panel 150
| Cabinet width | Capacity (modules type S, 18 mm) | Catalogue number |
|---|---|---|
| 600 mm | 24 | W-4881-68-01-011 |
| 800 mm | 36 | W-4881-68-02-011 |
| 1000 mm | 48 | W-4881-68-03-011 |
| 1200 mm | 48 | W-4881-68-04-011 |
Blank module plates
| Cabinet width | Height 150 mm | Height 100 mm | Height 50 mm |
|---|---|---|---|
| 600 mm | W-4881-68-05-011 | W-4881-71-01-011 | W-4881-72-01-011 |
| 800 mm | W-4881-68-06-011 | W-4881-71-02-011 | W-4881-72-02-011 |
| 1000 mm | W-4881-68-07-011 | W-4881-71-03-011 | W-4881-72-03-011 |
| 1200 mm | W-4881-68-08-011 | W-4881-71-04-011 | W-4881-72-04-011 |
Cover strips
| Version | For enclosure | Catalogue number |
|---|---|---|
| Vertical cover strips | Height 2000 mm | W-4881-69-02-011 |
| Vertical cover strips | Height 2200 mm | W-4881-69-04-011 |
| Horizontal cover strips | Width 600 mm | W-4881-70-01-011 |
| Horizontal cover strips | Width 800 mm | W-4881-70-02-011 |
| Horizontal cover strips | Width 1000 mm | W-4881-70-03-011 |
| Horizontal cover strips | Width 1200 mm | W-4881-70-04-011 |
Module panels and blank plates with mounting elements, packing unit 1 pc. Cover strips: according to the current catalogue one set of two vertical or two horizontal strips with mounting elements.
Equipment shelves for the SZE2
For devices that stand rather than hang: the equipment shelves are fixed directly to the enclosure frame, are powder-coated in RAL 7035 and carry 100 kg – the 754 × 390 mm shelf for 800 × 500 mm enclosures carries 200 kg. According to the catalogue, ZPAS makes other dimensions on request.

| Cabinet width | Rack depth | Dimensions | Load capacity | Perforated | Catalogue number |
|---|---|---|---|---|---|
| 600 mm | 600 mm | 552 × 540 × 25 mm | 100 kg | no | W-5899-09-00-011 |
| 800 mm | 600 mm | 752 × 530 × 25 mm | 100 kg | yes | W-5899-11-00-011 |
| 800 mm | 500 mm | 754 × 390 × 33 mm | 200 kg | no | W-8041-A1-67-011 |
| 600 mm | 800 mm | 552 × 730 × 25 mm | 100 kg | yes | W-6138-61-00-011 |
| 800 mm | 800 mm | 752 × 730 × 25 mm | 100 kg | yes | W-6412-62-00-011 |
Load capacity according to the catalogue. Supplied with fixing accessories, packing unit 1 pc. For 19″ devices there are separate 19″ equipment shelves.
Frequently asked questions
CLASSIC or UNI – what is the difference?
CLASSIC is built on supports: cross members and vertical supports are fixed to the enclosure frame or to the floor and roof plates, and the CLASSIC mounting rails, available in 25 lengths from 200 to 1200 mm, sit on them. UNI is a universal profile whose perforation matches the perforations in the enclosure frame; with angle connectors it forms any kind of frame, including the 19″ frame and the substructure of the module system. Both systems use the same fixing sets and can be combined.
Mounting plate or rail frame – which carries more?
For the SZE2 the catalogue gives 1,000 kg for the mounting plate and 1,600 kg for the mounting rail frame. The mounting plate is a closed surface for devices, ducts and DIN rails and is part of the standard delivery; a rail frame creates mounting levels at any depth.
Do the SZE2 rails also fit the SZE3?
No. The SZE3 has its own 25 mm grid on two levels; for this there are type A and B mounting rails for frames and type C for the 19″ frame. The same are the fixing sets with thread-forming screws M6 × 16 or cage nuts M6, as well as the 19″ profile rails, brackets and cross members.
When is the module system worthwhile?
When a distribution board with many modular devices is built in the SZE2: the devices sit on DIN rails behind module panels, with protection against contact to IP 30. A 2000 mm high enclosure takes 288 modules of 18 mm at 600 mm width, 432 at 800 mm and 576 at 1000 and 1200 mm.
Are rails and shelves available in special lengths?
Yes. UNI mounting rails are supplied in other lengths on request or cut to size individually, and ZPAS also manufactures equipment shelves in other dimensions on request. State the enclosure size and the length you need in your enquiry – or request the complete frame.
Mounting system put together?
Send us catalogue numbers and quantities – or the enclosure size and a list of devices, and we will put the frame together. Quotation within 2 working days at most.