Outdoor server cabinet:
19″ equipment outdoors
When servers, switches and UPS have to stand outside – at the mast, by the track, in the field – you need more than a sheet metal box: the ZPAS outdoor server cabinet combines the double-walled SZD aluminium series with a 19″ mounting level, climate control and access control. Direct from the manufacturer, in any special size.
Request a quote Configure an outdoor cabinetThe ZPAS outdoor server rack is a weatherproof 19-inch cabinet made of double-walled aluminium (SZD series) for servers, switches and UPS outdoors: IP 54/55, IK10, operating range −40 to +70 °C.
Server rack and outdoor enclosure in one
An outdoor server rack has to master two worlds at once: the 19″ world with profile rails, cable management and defined cooling air – and the outside world with rain, sun, frost and unauthorised hands. For this, ZPAS fits the double-walled SZD aluminium series with an integrated 19-inch level: the air layer in the double wall slows solar heat on its way into the interior, while climate control and heating keep the internal temperature within the window that the built-in equipment needs (depending on the device, e.g. 10–40 °C) – the enclosure’s operating range of −40 to +70 °C applies to the outside.
By the way: if you search for ZPAS SZD cabinets, you will also find them in IT resellers’ catalogues – ex works you get the same base in a special size, with prepared cut-outs, mounted climate control and a quotation within 2 working days at most, directly from the technical team.
Fit-out examples: what an equipped outdoor server cabinet looks like






Typical applications
Mobile & microwave radio
Baseband, transmission and battery equipment at the foot of the mast – compact, EMC-compliant, vandal-resistant.
Edge & network nodes
Active network equipment and edge servers outside the building – the complement to the container data centre.
Transport & rail
Trackside equipment, cameras and communication on road and rail – details on the rail & transport technology page.
Energy & generation
SCADA, telecontrol and communication at PV parks, wind sites and substations.
Industrial outdoor sites
Wi-Fi, positioning and process IT on factory sites, in ports and on logistics areas.
UPS & batteries outdoors
Uninterruptible power supply in an outdoor cabinet – for sizing, see UPS & battery cabinets.
Requirements – clearly classified
Double wall against the sun
The air layer between the shells slows radiant heat on its way to the IT – active cooling can be smaller or omitted altogether.
Climate control to suit the load
Filter fan, heat exchanger, CVO outdoor cooling unit or AHP heat pump plus heater – sized to IEC 60890 with the cooling capacity calculator.
Protection & access
IP 54/55, IK10, lockable doors with 2-point espagnolette lock (alternative lock cylinders on request).
19″ fit-out ex works
Profile rails, cable routes, PDU preparation and earthing are mounted ex works – on site, the IT just needs to be slid in.

Dimensions: width, depth and usable rack units
The outdoor server cabinet is based on the grid of the SZD series. Width and depth follow the standard dimensions from the catalogue; you specify the height freely. For the 19″ equipment, the internal dimension is what counts: in width and depth it is 126 mm less than the external dimension in each case.
| External width W | Internal width W1 | Door |
|---|---|---|
| 409 mm | 283 mm | single door |
| 509 mm | 383 mm | single door |
| 609 mm | 483 mm | single door |
| 709 mm | 583 mm | single door |
| 809 mm | 683 mm | single door |
| 1,009 mm | 883 mm | single door |
| 1,154 mm | 1,028 mm | double door |
| 1,254 mm | 1,128 mm | double door |
| 1,354 mm | 1,228 mm | double door |
| 1,453 mm | 1,328 mm | double door |
| 1,554 mm | 1,428 mm | double door |
| 1,654 mm | 1,528 mm | double door |
- Depth: standard depths 409 · 509 · 609 · 709 · 809 · 1,009 mm, internal 283 to 883 mm. The depth is determined by the deepest installed device plus connection and cable space.
- Height: freely selectable. The usable height in the cabinet is the cabinet height minus 120 mm; the plinth height is added as required.
- 19″ level: the swing frame has a mounting width of 456 mm (21″: 515 mm), a usable width of 442 mm and is 504 mm wide. It is available with one or two sections, and as a box-type frame for higher loads.
- Usable rack units: for the swing frame, the usable height is the frame height minus 120 mm; one U measures 44.45 mm. Worked example: a frame 1,800 mm high has a usable height of 1,680 mm, which is 37 U. A battery compartment in the lower part of the cabinet shortens the 19″ level accordingly.
Special sizes are possible in every direction, including cabinets with more than two doors. All dimensional drawings are in the outdoor cabinets catalogue from p. 14, the swing frame on p. 29 (PDF). The series at a glance: standard dimensions of the SZD outdoor cabinets.
Climate control in the outdoor server cabinet
Outdoors, two loads come together: the power loss of the IT and, in summer, the sun on the enclosure. In winter there is a risk of frost and condensation. Which technology fits depends above all on whether it has to stay cooler inside the cabinet than outside.
- Forced ventilation with ventilation panel: for moderate heat loads, when the internal temperature may be above the outside temperature. In winter, an air heater with 400 W and thermostat maintains the temperature.
- Dual air circulation: for sites in full sun. An outer airflow carries the solar heat away between the double walls; the inner circuit remains separated from the outside air.
- Cross-flow heat exchanger or direct ventilation: for high heat loads, typically with UPS installations. Direct ventilation works with two fans of 510 m³/h each.
- CVO cooling unit: compressor cooling with 525 to 5,800 W, when the internal temperature is to be below the outside temperature.
- AHP heat pump: cools and heats with one unit. The AHP_35_Ti maintains 10–40 °C and 32–72 % relative humidity; the AHP 7.0 delivers 7 kW of cooling and 9 kW of heating.
Servers and active network equipment have a narrow temperature window. For them, the route therefore usually leads to the cooling unit or the heat pump, because in summer it has to stay cooler inside than outside. The starting figure is the electrical power consumption of the devices: it becomes heat in the cabinet. The guide value to IEC 60890 is provided by the cooling capacity calculator; outdoors, the solar load comes on top. All methods with pictures and a selection table are shown on the outdoor climate control page. The unit is supplied sized, mounted and wired ex works.
Outdoor network cabinet: smaller equipment sites
Not every outdoor site needs server depth. For switches, patch panels, routers and a small power supply, an outdoor network cabinet is enough: the same SZD construction with double wall, IP 54/55 and IK10, but in smaller dimensions.
- Dimensions: network equipment is shallow. Instead of 1,009 mm, the smaller standard depths are often sufficient; up to a width of 1,009 mm the cabinet has a single door.
- Mounting: small cabinets can be fixed with wall or pole brackets; larger ones stand on a plinth, foundation frame or concrete foundation.
- Climate control: with a moderate heat load, forced ventilation with a ventilation panel is often enough, plus the air heater against frost and condensation.
- Access: the 19″ swing frame makes the rear of the equipment accessible without clearing out the cabinet. It is locked with a 2-point espagnolette lock.
Typical sites are network nodes at the roadside, equipment at the foot of a mast, and cameras and communication on road and rail. The requirements of the sector are summarised on the page Telecommunications & edge network nodes. For network cabinets inside buildings there is a separate overview: 19-inch network cabinets.
Why ZPAS for outdoor IT
Because both trades come from a single source: enclosure construction and 19″ fit-out, climate control and access control – planned, manufactured and tested ex works, in any special size and repeatable for roll-outs after drawing approval. The basic design takes minutes in the outdoor cabinet configurator; for the climate question alone, see the overview server rack climate control.
Frequently asked questions – outdoor server rack
What is an outdoor server rack?
A weatherproof enclosure with an integrated 19″ mounting level for servers, switches, UPS and radio equipment outdoors – at ZPAS based on the double-walled SZD series: IP 54/55, IK10, −40 to +70 °C.
How is the IT in an outdoor cabinet cooled and heated?
Passively by the double wall, plus filter fan, heat exchanger, CVO cooling unit or AHP heat pump – and heating against condensation and frost. Sizing to IEC 60890 with the cooling capacity calculator. Plinth, foundation frame and other outdoor accessories are added ex works.
What do I get if I order direct from the factory?
Ex works you get any special size, prepared cut-outs, mounted climate control and 19″ fit-out – with a quotation within 2 working days at most, directly from the technical team.
Can access be controlled at an outdoor site?
Yes – electronic handles, door contacts, sensors and a camera log every access; alarms are sent by email/SMS.
View completed outdoor projects
Twenty-one delivered orders in pictures, ten of them on site – from the Formula 1 circuit in Jeddah to an installation in Togo. Plus special colours, rows up to 4,700 mm, roof-mounted climate control, 19-inch and electrical interior fit-outs.
View referencesPlanning an outdoor IT project?
Site, equipment list and heat load are all we need – design and quotation within 2 working days at most.