Outdoor server cabinet:
19″ equipment outdoors

When servers, switches and UPS have to stand outside – at the mast, by the track, in the field – you need more than a sheet metal box: the ZPAS outdoor server cabinet combines the double-walled SZD aluminium series with a 19″ mounting level, climate control and access control. Direct from the manufacturer, in any special size.

Request a quote Configure an outdoor cabinet

The ZPAS outdoor server rack is a weatherproof 19-inch cabinet made of double-walled aluminium (SZD series) for servers, switches and UPS outdoors: IP 54/55, IK10, operating range −40 to +70 °C.

Server rack and outdoor enclosure in one

An outdoor server rack has to master two worlds at once: the 19″ world with profile rails, cable management and defined cooling air – and the outside world with rain, sun, frost and unauthorised hands. For this, ZPAS fits the double-walled SZD aluminium series with an integrated 19-inch level: the air layer in the double wall slows solar heat on its way into the interior, while climate control and heating keep the internal temperature within the window that the built-in equipment needs (depending on the device, e.g. 10–40 °C) – the enclosure’s operating range of −40 to +70 °C applies to the outside.

By the way: if you search for ZPAS SZD cabinets, you will also find them in IT resellers’ catalogues – ex works you get the same base in a special size, with prepared cut-outs, mounted climate control and a quotation within 2 working days at most, directly from the technical team.

Fit-out examples: what an equipped outdoor server cabinet looks like

19″ equipment at the top, battery compartment at the bottom – two-door outdoor server cabinet, fitted out at the factory
19″ equipment at the top, battery compartment at the bottom – two-door outdoor server cabinet, fitted out at the factory
Telecommunications equipment with power supply and battery in a two-door cabinet
Telecommunications equipment with power supply and battery in a two-door cabinet
System equipment on two 19″ levels, blanking panel for later expansion
System equipment on two 19″ levels, blanking panel for later expansion
Single-door cabinet with rectifier modules and 19″ equipment
Single-door cabinet with rectifier modules and 19″ equipment
Two 19″ frames, prepared for the operator’s equipment
Two 19″ frames, prepared for the operator’s equipment
On site: placed on a foundation, 19″ equipment and batteries in the lower compartment
On site: placed on a foundation, 19″ equipment and batteries in the lower compartment

Typical applications

Mobile & microwave radio

Baseband, transmission and battery equipment at the foot of the mast – compact, EMC-compliant, vandal-resistant.

Edge & network nodes

Active network equipment and edge servers outside the building – the complement to the container data centre.

Transport & rail

Trackside equipment, cameras and communication on road and rail – details on the rail & transport technology page.

Energy & generation

SCADA, telecontrol and communication at PV parks, wind sites and substations.

Industrial outdoor sites

Wi-Fi, positioning and process IT on factory sites, in ports and on logistics areas.

UPS & batteries outdoors

Uninterruptible power supply in an outdoor cabinet – for sizing, see UPS & battery cabinets.

Requirements – clearly classified

Double wall against the sun

The air layer between the shells slows radiant heat on its way to the IT – active cooling can be smaller or omitted altogether.

Climate control to suit the load

Filter fan, heat exchanger, CVO outdoor cooling unit or AHP heat pump plus heater – sized to IEC 60890 with the cooling capacity calculator.

Protection & access

IP 54/55, IK10, lockable doors with 2-point espagnolette lock (alternative lock cylinders on request).

19″ fit-out ex works

Profile rails, cable routes, PDU preparation and earthing are mounted ex works – on site, the IT just needs to be slid in.

Open ZPAS outdoor server cabinet with 19-inch level and climate control

Dimensions: width, depth and usable rack units

The outdoor server cabinet is based on the grid of the SZD series. Width and depth follow the standard dimensions from the catalogue; you specify the height freely. For the 19″ equipment, the internal dimension is what counts: in width and depth it is 126 mm less than the external dimension in each case.

External width WInternal width W1Door
409 mm283 mmsingle door
509 mm383 mmsingle door
609 mm483 mmsingle door
709 mm583 mmsingle door
809 mm683 mmsingle door
1,009 mm883 mmsingle door
1,154 mm1,028 mmdouble door
1,254 mm1,128 mmdouble door
1,354 mm1,228 mmdouble door
1,453 mm1,328 mmdouble door
1,554 mm1,428 mmdouble door
1,654 mm1,528 mmdouble door

Special sizes are possible in every direction, including cabinets with more than two doors. All dimensional drawings are in the outdoor cabinets catalogue from p. 14, the swing frame on p. 29 (PDF). The series at a glance: standard dimensions of the SZD outdoor cabinets.

Climate control in the outdoor server cabinet

Outdoors, two loads come together: the power loss of the IT and, in summer, the sun on the enclosure. In winter there is a risk of frost and condensation. Which technology fits depends above all on whether it has to stay cooler inside the cabinet than outside.

Servers and active network equipment have a narrow temperature window. For them, the route therefore usually leads to the cooling unit or the heat pump, because in summer it has to stay cooler inside than outside. The starting figure is the electrical power consumption of the devices: it becomes heat in the cabinet. The guide value to IEC 60890 is provided by the cooling capacity calculator; outdoors, the solar load comes on top. All methods with pictures and a selection table are shown on the outdoor climate control page. The unit is supplied sized, mounted and wired ex works.

Outdoor network cabinet: smaller equipment sites

Not every outdoor site needs server depth. For switches, patch panels, routers and a small power supply, an outdoor network cabinet is enough: the same SZD construction with double wall, IP 54/55 and IK10, but in smaller dimensions.

Typical sites are network nodes at the roadside, equipment at the foot of a mast, and cameras and communication on road and rail. The requirements of the sector are summarised on the page Telecommunications & edge network nodes. For network cabinets inside buildings there is a separate overview: 19-inch network cabinets.

Why ZPAS for outdoor IT

Because both trades come from a single source: enclosure construction and 19″ fit-out, climate control and access control – planned, manufactured and tested ex works, in any special size and repeatable for roll-outs after drawing approval. The basic design takes minutes in the outdoor cabinet configurator; for the climate question alone, see the overview server rack climate control.

Frequently asked questions – outdoor server rack

What is an outdoor server rack?

A weatherproof enclosure with an integrated 19″ mounting level for servers, switches, UPS and radio equipment outdoors – at ZPAS based on the double-walled SZD series: IP 54/55, IK10, −40 to +70 °C.

How is the IT in an outdoor cabinet cooled and heated?

Passively by the double wall, plus filter fan, heat exchanger, CVO cooling unit or AHP heat pump – and heating against condensation and frost. Sizing to IEC 60890 with the cooling capacity calculator. Plinth, foundation frame and other outdoor accessories are added ex works.

What do I get if I order direct from the factory?

Ex works you get any special size, prepared cut-outs, mounted climate control and 19″ fit-out – with a quotation within 2 working days at most, directly from the technical team.

Can access be controlled at an outdoor site?

Yes – electronic handles, door contacts, sensors and a camera log every access; alarms are sent by email/SMS.

All questions in the FAQ →
ZPAS outdoor cabinet, free-standing on a village through road
References

View completed outdoor projects

Twenty-one delivered orders in pictures, ten of them on site – from the Formula 1 circuit in Jeddah to an installation in Togo. Plus special colours, rows up to 4,700 mm, roof-mounted climate control, 19-inch and electrical interior fit-outs.

View references

Planning an outdoor IT project?

Site, equipment list and heat load are all we need – design and quotation within 2 working days at most.