Server room cooling

Cool the whole room, the rack row or the individual rack? The answer depends on the heat load per rack and on the number of racks. This page sets out the three levels and shows which one fits when.

Request a quote Calculate cooling capacity

Three levels: room, row, rack

Server room cooling removes the heat of the IT from the room. Every watt drawn by servers, switches and UPS becomes heat. Cooling takes place on one of three levels: the whole room, the rack row or the individual rack.

Level 1 · Room

Room cooling

The air conditioning supplies the whole room, generally with cold air via the perforated raised floor. Racks with perforated doors let the cold air through; blanking panels and cold/hot aisle separation prevent short-circuit air.

approx. 1.5–5 kW per rack Z-SERVER with perforated doors →
Level 2 · Row

In-row cooling

The cooling unit stands between the racks, draws warm air from the hot aisle and blows cold air directly into the cold aisle. The air path is short, the temperature difference high. Containment is a prerequisite.

from approx. 6 kW per rack · 11.2–37.7 kW per unit Databox containment →
Level 3 · Rack

Rack cooling

The rack is closed to IP 54 or higher and cools in its own circuit: with a side-mounted cooling unit CVE, a roof-mounted cooling unit ETE or an air/water heat exchanger CNW. The room itself does not need to be air-conditioned for this.

310–5,800 W per unit Server rack cooling →

Which level fits when

The table is a guide for preselection, not a design calculation. The decisive factors are the heat load per rack, the number of racks and what the room already provides.

Starting pointLevelEquipmentPrerequisite
A few racks, up to approx. 1.5 kW per rackVentilationPerforated doors, filter fan LV with outlet filter GVRoom cooler than the permissible internal temperature
Server room with approx. 1.5–5 kW per rackRoomRoom air conditioning with organised cold/warm air routingBlanking panels, cold/hot aisle arrangement
Several racks in a row, from approx. 6 kW per rackRowIn-row heat exchanger BWC-DX2 (11.2 kW), precision air conditioning KWT (12.3–37.7 kW)Containment; a chilled-water network for KWT
No chilled water, waste heat has to leave the roomRowDirect expansion (DX) with external condenser, 4.4–22.3 kWLocation for the outdoor unit, refrigerant lines
Single rack without room cooling, warm or dusty roomRackCompressor cooling unit CVE/ETE, 310–5,800 WRack closed to IP 54 or higher
Single rack, chilled-water network availableRackAir/water heat exchanger CNW, 900–3,000 WFlow temperature, flow rate and pressure known

For AI and GPU racks with 30–100 kW per rack, none of these levels is sufficient on its own; the requirements are described in the guide Server racks for AI & GPU. If the room does not exist yet, the micro data centre or the container data centre is the way to go.

Heat load per rack: the worked example

For IT equipment, the simplified rule is: all the electrical power drawn is converted into heat. 1 kW of power consumption means 1 kW of waste heat. The calculation uses the actual consumption of the devices, not the rated power of the power supplies; the actual consumption is typically 40–60 % of the rated value.

Step 1 · Rack

One rack

10 servers with an actual consumption of 400 W each give 4,000 W, two switches at 150 W each a further 300 W. On top of that come around 200 W of UPS losses.

4.5 kW of waste heat per rack
Step 2 · Room

Six racks

Six identically equipped racks give off 6 × 4.5 kW = 27 kW to the room. With a 15 % reserve for peak loads and expansion, that makes around 31 kW.

approx. 31 kW cooling requirement in the room
Step 3 · Level

The conclusion

At 4.5 kW per rack, the room is on the borderline between room cooling and in-row cooling. Arithmetically, three in-row heat exchangers with 11.2 kW each cover the load, calculated without redundancy.

3 × 11.2 kW = 33.6 kW

The example shows the calculation method; it does not replace a design calculation. The guide value for the individual rack is provided by the cooling capacity calculator to IEC 60890. The calculation for the rack is explained in the guide What is a server rack?

Containment: the lever at room level

Without containment, cold supply air and warm exhaust air mix across the rows, and the air conditioning has to supply colder air in greater volumes. Cold aisle or hot aisle containment eliminates this mixing and reduces cooling energy demand by up to 40 %. It is recommended from five to six racks or from 5 kW per rack.

At ZPAS, the containment is available as the Databox: sliding doors, roof modules and aisle lighting for the 1,200 mm wide aisle, based on Z-SERVER, SZB IT or DSR IT. It can be integrated into existing server rooms without any conversion work and extended by further rack rows.

Free cooling systems additionally use the outside air: up to 70 % less cooling energy, depending on location. The system overview is on the page Data centre & server room solutions.

Frequently asked questions – server room cooling

Room cooling or in-row cooling: when is it worth switching?

From about 6 kW per rack and with several racks in a row, it is no longer the room that is cooled but the rack row. The cooling unit then stands between the racks, draws warm air from the hot aisle and blows cold air into the cold aisle. The prerequisite is clean cold/hot aisle separation.

How much cooling capacity does a server room need?

The electrical power drawn by the IT is converted entirely into heat: 1 kW of power means 1 kW of waste heat. Add up the actual consumption of all devices, add 3 to 6 per cent for UPS losses and a 10 to 20 per cent reserve. Six racks at 4.5 kW each give 27 kW of waste heat and, with a 15 per cent reserve, a cooling requirement of around 31 kW.

Does a single server rack need an air-conditioned room?

No. A closed rack of IP 54 or higher with a compressor cooling unit cools in its own circuit, regardless of the room temperature. However, the waste heat from the cooling unit stays in the installation room; with several units in a small plant room, the room itself needs ventilation or cooling. The units are shown on the server rack cooling page.

What does cold aisle containment achieve?

It separates cold supply air from warm exhaust air and reduces cooling energy demand by up to 40 per cent. It is recommended from five to six racks or from 5 kW per rack. At ZPAS, the containment is available as the Databox.

Have your server room cooling designed

Number of racks, heat load per rack and the room situation are all we need – we will get back to you with a concept.